Frequency to Voltage Converter | ||
Model # F to V-1 | ||
Features:High speed optically isolated input Output can be isolated from ground Din Rail Mounting Output offset and gain adjustment High Linearity +- .01% max at 10Khz Max input frequency 500 kHz |
Connections | |
Applications:Tachometer High noise immunity data link |
Layout | |
AdjustmentsP2 Frequency to voltage Gain P1 Offset
F/V-1 Calibration: 1. Apply power to the module. 2. Connect VoltMeter NEG(-) to pin E and connect POS(+) to pin F for positive voltage out or pin D for negative voltage out. 3. Turn P1 and P2 full CCW (about 20 turns) 4. Now turn P2 1 turn CW 5. Next, set P1 to deliver 0vdc output or other voltage if desired. There should be no pulses going into the module at this time. 6. Now turn your pulse generator on. Run it up to full speed and set desired output voltage using P2. Typically this about 10vdc output. 7. Now decrease speed by half. Now check your voltage it should be half of your full speed setting. If this is true you have now setup your module. |
||