Adjustments
MAO-2 CALIBRATION INSTRUCTIONS
1. Connect the power supply ,input voltage, and load (50-500 ohm)
as shown in the installation diagram.
2. Connect a current meter in series with the load.
3. With 0 volts input, adjust offset pot P2 until the current
output is 4mA.
4. Apply a 10 volt input and adjust the span pot P1 until the
current output is 20mA.
The out put current will now vary 4 to 20 mA with a 0-10 volts
input. The current is independent of the load with in the
specified range.
|